Transformer sizing on the 2026 NEC: Table 450.5(B), step by step
On the 2023 NEC you sized transformer protection from Table 450.3(B). On the 2026 NEC the same table, with the same percentages, sits at Table 450.5(B). The question type has not changed. What changed is where you find it, and the rounding notes are where most wrong answers come from. This guide walks the table the way the exam uses it.
The percentages that matter (1,000 V and below)
Table 450.5(B) gives maximum overcurrent device ratings as a percentage of rated transformer current. For a transformer protected on the primary side only:
| Rated primary current | Maximum primary device | Rounding rule |
|---|---|---|
| 9 A or more | 125% | Note 1 applies: you may round up to the next higher standard rating in 240.6(A) |
| 2 A to less than 9 A | 167% | No next-size-up permission |
| Less than 2 A | 300% | No next-size-up permission |
Primary plus secondary protection
If you protect both sides, the primary device may be up to 250% of rated primary current, and Note 1 does not apply to that row: you may not round up past 250%. The secondary device is then 125% for rated currents of 9 A or more (Note 1 rounding allowed) and 167% below 9 A. Most exam questions use this primary-plus-secondary arrangement because it tests both rounding rules in one question.
Worked example: 75 kVA, 480 V to 208Y/120 V, three-phase
Step 1, rated primary current: 75,000 VA ÷ (480 V × 1.732) = 90.2 A. Step 2, rated secondary current: 75,000 VA ÷ (208 V × 1.732) = 208.2 A.
Option A, primary protection only: 90.2 A is 9 A or more, so 125% × 90.2 = 112.8 A. Note 1 lets you round up to the next standard size in 240.6(A): a 125 A device.
Option B, primary plus secondary: the primary at 250% × 90.2 = 225.5 A, and because Note 1 does not apply, the largest standard device that does not exceed it is 225 A. The secondary at 125% × 208.2 = 260.2 A, with Note 1 rounding up to the next standard size: 300 A.
The two traps: rounding the 250% primary value up to 250 A (not allowed), and treating 125% as a hard cap when Note 1 actually lets you go to the next standard size.
How to tab your book
- Table 450.5(B) — one tab; this table is the whole question type.
- The notes directly under the table — Note 1 is the rounding rule the exam tests.
- 240.6(A) — standard ampere ratings, needed for every rounding step.
- 450.5(A) — transformers over 1,000 V, which shows up as a distractor.
Practice it
Transformer protection shows up on almost every Texas journeyman form. Our free 20-question diagnostic includes one and scores each calculation type separately, so you can see exactly where the points leak. No sign-up.
Check yourself in 30 minutes
Our free 20-question diagnostic is built on the 2026 NEC and scores each exam portion separately. No sign-up.
Take the free diagnostic See the full Texas Journeyman Electrician packSources
- EC&M: Safeguarding transformers and conductors — primary and secondary protection percentages
- 2026 NEC transformer protection table (450.5(B)), reproduced in a code-change summary
Updated 2026-11-24. Found something wrong? Tell us and we will fix it and log the fix on our quality page.