Conduit fill worked examples: Chapter 9 of the NEC, step by step
Conduit fill questions are pure table work: get the raceway area from Chapter 9 Table 4, the conductor areas from Table 5, and compare against the percentages in Table 1. The values did not change between the 2023 and 2026 NEC. What separates a pass from a fail is doing the lookup fast, and knowing when Annex C lets you skip the math entirely.
The three percentages (Chapter 9, Table 1)
Table 1 caps total conductor cross-section as a share of the raceway's inside area, for every raceway type:
| Conductors in the raceway | Maximum fill |
|---|---|
| 1 conductor | 53% |
| 2 conductors | 31% |
| 3 or more conductors | 40% |
Notes the exam likes
- A nipple of 24 in or less may be filled to 60% (Table 1, Note 4).
- Equipment grounding conductors count as conductors for fill.
- The 31% column for exactly two conductors is a classic trap — most people only remember 40%.
- Tables 4 and 5 already contain the 40% column and the conductor areas. You rarely need to compute a circle area by hand.
Example 1: 12 AWG THHN in 1/2 in EMT — skip the math
When every conductor is the same size and insulation type, Annex C does the work. Table C.1 (EMT) lists the maximum number of 12 AWG THHN conductors in 1/2 in EMT directly: 9.
On the exam, always check whether the question is an Annex C case before reaching for Tables 4 and 5. It is the difference between 20 seconds and 3 minutes.
Example 2: mixed sizes — 3× 6 AWG THHN plus 1× 10 AWG THHN in EMT
Mixed sizes are not in Annex C, so this is a Table 4 plus Table 5 problem. From Table 5: 6 AWG THHN = 0.0507 in², 10 AWG THHN = 0.0211 in².
Total conductor area: 3 × 0.0507 + 0.0211 = 0.1521 + 0.0211 = 0.1732 in². Four conductors means the 40% column of Table 4.
1/2 in EMT at 40% allows 0.122 in² — not enough. 3/4 in EMT at 40% allows 0.213 in² — that fits. Answer: 3/4 in EMT.
If you want to check a fill you are pulling on site, our free conduit fill tool does the same lookup: /exams/tools/conduit-fill.
How to tab your book
- Chapter 9 Table 1 — the percentages and the nipple note.
- Chapter 9 Table 4 — raceway areas, with the 40% column marked.
- Chapter 9 Table 5 — conductor areas for THHN/THWN/THWN-2.
- Annex C, Table C.1 (EMT) — same-size conductors, the fast path.
Practice it
Raceway and box fill are among the most-tested calculation types on the Texas journeyman exam. The free 20-question diagnostic scores them as their own category, so you can see whether tables or theory are costing you more. No sign-up.
Check yourself in 30 minutes
Our free 20-question diagnostic is built on the 2026 NEC and scores each exam portion separately. No sign-up.
Take the free diagnostic See the full Texas Journeyman Electrician packSources
- EC&M (ecmweb): Conduit and raceway changes in the 2026 NEC
- PSI Candidate Information Bulletin: Texas electrician exams, 2026 NEC references
Updated 2026-11-24. Found something wrong? Tell us and we will fix it and log the fix on our quality page.