2026 NEC grounding and bonding changes: what moved and what the exam will ask

Grounding and bonding is one of the heaviest question families on the Texas journeyman exam, and Article 250 saw more revision this cycle than in the previous two. The good news: most values you memorized still hold. The risk is structural: rules you could find blindfolded now sit in new places.

The big structural move

In the 2023 NEC, Article 250 covered everything including systems over 1,000 volts in its Part X. In the 2026 NEC, Article 250 covers only installations up to 1,000 volts ac and 1,500 volts dc, and the over-1,000-volt rules moved into five new Chapter 2 articles: 265 (branch circuits), 266 (feeders), 267 (outside circuits), 268 (services) and 270 (grounding and bonding over 1,000 volts).

Article 250 now has nine parts instead of ten. Sections 250.1 (scope) and 250.4 (general requirements) were rewritten to match the new structure and to state clearly that the article covers both system grounding and equipment grounding and bonding.

250.122: the EGC sizing rule was rewritten

Section 250.122, the rule for sizing equipment grounding conductors, got a substantial rewrite intended to simplify application. The most consequential shift is in parallel conductor sizing, now organized in 250.122(H).

Table 250.122 itself is still the table you size from, so your tab stays valid, but the surrounding subsections moved. If you learned the old layout by heart, re-walk the section once with the 2026 book before exam day.

Installation rules that tightened

  • 250.64(C) and 250.70: below-grade grounding electrode conductor connections now expect irreversible compression connectors listed for grounding and bonding, or exothermic welding; an older exception some inspectors accepted was removed.
  • 250.64(A): aluminum and copper-clad aluminum grounding electrode conductors cannot terminate within 18 inches of earth and cannot be used outdoors in contact with masonry.
  • 250.104: bonding of corrugated stainless steel gas tubing (CSST) is now referenced explicitly, with a minimum 6 AWG copper bonding jumper.
  • 250.94: the intersystem bonding termination must be accessible and listed.

What this means for your exam prep

  • Keep your Table 250.122 and Table 250.66 tabs; both tables still carry the answers.
  • Re-read 250.122 in the 2026 book, especially the parallel sizing subsection, so the new layout is familiar before the clock starts.
  • For anything over 1,000 volts, look in Articles 265 to 270, not Article 250. The journeyman exam rarely goes there, but a lookup question can.
  • Grounding questions reward exact section knowledge. If grounding was a weak domain on your diagnostic, this is the article to drill.