1. A PV module has Voc = 49.5 V at STC and a Voc temperature coefficient of −0.27 %/°C. The lowest expected ambient temperature at the site is −18 °C. Using the manufacturer coefficient method, what is the module's maximum Voc?
ΔT = −18 − 25 = −43 °C. Correction = 1 + (−0.0027 × −43) = 1.1161. Voc,max = 49.5 × 1.1161 = 55.2 V.
Reference: 2017 NEC 690.7(A)(1)
2. A module's temperature-corrected maximum Voc is 55.2 V. The inverter's maximum DC input voltage is 600 V. What is the maximum number of modules in one series string?
600 ÷ 55.2 = 10.87. Always round down: 10 modules. Eleven would give 11 × 55.2 = 607 V, above the 600 V limit.
Reference: 2017 NEC 690.7(A)
3. A monofacial module has a rated Isc of 13.9 A. Using 125% of the rated Isc, what is the maximum circuit current of a single PV source circuit?
Maximum circuit current = Isc × 1.25 = 13.9 × 1.25 = 17.4 A.
Reference: 2017 NEC 690.8(A)(1)
4. A PV source circuit has a maximum circuit current of 17.4 A. If an overcurrent device is installed and it is not part of an assembly listed for 100% continuous operation, what is the smallest standard rating that meets the continuous-current requirement?
OCPD ≥ 1.25 × 17.375 A = 21.7 A. The next standard size is 25 A. (Check that it does not exceed the module's maximum series fuse rating.)
Reference: 2017 NEC 690.9(B), 240.6(A)
5. A 2-wire DC circuit carries 10.5 A over a one-way length of 150 ft in #10 copper (use 1.24 Ω per 1,000 ft). The circuit operates at 400 V. What is the voltage drop as a percentage?
VD = 2 × L × I × R ÷ 1000 = 2 × 150 × 10.5 × 1.24 ÷ 1000 = 3.91 V. 3.91 ÷ 400 = 0.98 %. A common mistake is to forget the factor 2 (the current goes out and back).
6. A single-phase inverter has a continuous output current rating of 32 A at 240 V. Using a standard breaker that is not listed for 100% continuous operation, what is the minimum standard size of its output overcurrent device?
Use the inverter's rated continuous output current, not kW ÷ V: 32 A × 1.25 = 40 A, which is a standard size. 35 A forgets the 125% factor.
Reference: 2017 NEC Article 705 (inverter output circuit at 125%), 240.6(A)
7. A panelboard has a 200 A busbar and a 200 A main breaker. The PV backfed breaker will sit at the opposite end of the bus from the main. Under the 120 % rule, what is the most that 125 % of the inverter's rated output current may be?
120 % × 200 A = 240 A. 240 A − 200 A main = 40 A. So 125 % of the inverter output current may be at most 40 A, which allows an inverter of up to 32 A rated output (32 A is the trap answer).
Reference: 2017 NEC 705.12(B)(2)(3)(b)
8. An 8.4 kWdc array sees an average of 5.2 peak sun hours per day in the plane of the array. Total system derate is 0.80. Roughly how much energy will it produce in a year?
8.4 × 5.2 × 0.80 × 365 = 12,755 kWh ≈ 12,750 kWh. 15,940 kWh is the answer if you forget the derate.
9. Twenty 410 W modules feed a 6.0 kW (AC) inverter. What is the DC-to-AC ratio?
DC = 20 × 410 W = 8.2 kW. 8.2 ÷ 6.0 = 1.37.
10. A module has Vmp = 37.6 V at STC and a Vmp temperature coefficient of −0.35 %/°C. The highest expected cell temperature is 70 °C. The inverter's minimum MPPT voltage is 250 V. Ignoring module degradation and conductor voltage drop, what is the minimum number of modules per string?
ΔT = 70 − 25 = 45 °C. Vmp,hot = 37.6 × (1 − 0.0035 × 45) = 31.7 V. 250 ÷ 31.7 = 7.9. Always round up: 8 modules. In a real design, leave margin for degradation and voltage drop: 8 modules give only about 253 V when hot.
Your score: 0 / 10