2026 NEC changes that matter on the Texas journeyman exam

PSI's Candidate Information Bulletin for the Texas electrician exams says that from 1 September 2026 the exams are referenced to the 2026 NEC. The exam is open book, so the biggest risk is not a new rule. It is looking in the wrong place, or using a value that changed. These are the changes we found that matter most for the journeyman exam.

Moved sections and changed values

Topic2023 NEC2026 NECWhat it means on the exam
Load calculationsArticle 220Article 120 (Chapter 1)Tab Article 120. Books written for 2023 send you to Article 220.
Dwelling general lighting, feeder and service load3 VA/ft² (220.41)2 VA/ft² (120.41)Service and feeder answers come out lower. 3 VA/ft² is kept only for counting branch circuits (120.13).
Dwelling lighting demand factorsTable 220.45Table 120.45Same percentages: first 3,000 VA at 100%, next to 120,000 VA at 35%, rest at 25%.
Household rangesTable 220.55Table 120.55Same method, new number.
Optional dwelling calculation220.82: first 10 kVA at 100%120.82: first 8 kVA at 100%, rest at 40%; EVSE at 100% of nameplateOptional-method answers change.
Feeder overcurrent protection215.3215.5Same rule: 125% of continuous plus 100% of noncontinuous.
Transformer overcurrent protection450.3(B), Table 450.3(B)450.5(B), Table 450.5(B)Same percentages and next-size-up note.
Underground minimum cover300.5300.7Same depths: 24 in for direct-burial cable in general locations.
Tamper-resistant receptacles406.12406.26Same requirement, new number.
Dwelling 83% rule310.12310.12(A) services, 310.12(B) feedersNow only for conductors rated 75 °C or higher, so not for NM cable.

Worked example: the same house, two answers

A 2,000 ft² dwelling with the two required small-appliance circuits and one laundry circuit. General lighting, small-appliance and laundry load after demand factors, standard method:

2026 NEC: 2,000 × 2 VA = 4,000 VA, plus 3,000 VA small-appliance and 1,500 VA laundry = 8,500 VA. First 3,000 VA at 100% = 3,000 VA; the remaining 5,500 VA at 35% = 1,925 VA. Total: 4,925 VA.

2023 NEC: 2,000 × 3 VA = 6,000 VA, plus 4,500 VA = 10,500 VA. 3,000 VA + 7,500 VA × 35% = 5,625 VA.

On a 2026 exam, 5,625 VA is likely to be one of the wrong options. This exact question is number 12 in our free diagnostic.

How to tab your book

  • Article 120, with separate tabs for 120.41, 120.52, Table 120.45, Table 120.55 and 120.82.
  • 215.5 for feeder overcurrent protection and 240.6(A) for standard sizes.
  • Table 450.5(B) for transformers.
  • 300.7 and its minimum cover table.
  • 406.26 for tamper-resistant receptacles.
  • Check the PSI bulletin for which books and tabs are allowed in the exam room.

What did not change

In the 2026 change summaries we checked, the core tables most calculation questions use keep their numbers: Table 310.16 ampacities, the motor full-load current tables in Article 430 and the Chapter 9 conduit fill tables. The exam format is the same as since March 2025: a 59-question NEC Knowledge portion in 130 minutes and a 26-question Calculations portion in 110 minutes, 70% to pass each.

Check yourself in 30 minutes

Our free 20-question diagnostic is built on the 2026 NEC and scores each exam portion separately. No sign-up.

Take the free diagnostic See the full Texas Journeyman Electrician pack